Answer:
a) 0.813
b) 4.38 KW
c) COP = 5.13
d) 3.91 KW , COP = 6.17
Explanation:
Data obtained A-13 tables for R-134a:
[tex]h_{1} = 247.88 \frac{KJ}{kg} \\s_{1} = 0.9575 \frac{KJ}{kgK}\\h_{2s} = 279.45 \frac{KJ}{kg}\\h_{2} = 286.71 \frac{KJ}{kg}\\h_{3} = 87.83 \frac{KJ}{kg}[/tex]
The isentropic efficiency of the compressor is determined by :
[tex]n_{C} = \frac{h_{2s} - h_{1} }{h_{2} - h_{1} }\\= \frac{279.45 - 247.88 }{286.71 - 247.88}\\= 0.813[/tex]
The rate of heat supplied to the room is determined by heat balance:
[tex]Q = m(flow) * (h_{2} -h_{3})\\= (0.022)*(286.71 - 87.83)\\\\= 4.38KW[/tex]
Calculating COP
[tex]COP = \frac{Q_{H} }{W} \\COP = \frac{Q_{H} }{m(flow) * (h_{2} - h_{1}) }\\\\COP = \frac{4.38}{(0.022)*(286.71-246.88)}\\\\COP = 5.13[/tex]
Part D
Data Obtained:
[tex]h_{1} = 244.5 \frac{KJ}{kg} \\s_{1} = 0.93788 \frac{KJ}{kgK}\\h_{2} = 273.31 \frac{KJ}{kg}\\h_{3} = 95.48 \frac{KJ}{kg}[/tex]
The rate of heat supplied to the room is determined by heat balance:
[tex]Q = m(flow) * (h_{2} -h_{3})\\= (0.022)*(273.31 - 95.48)\\\\= 3.91KW[/tex]
Calculating COP
[tex]COP = \frac{Q_{H} }{W} \\COP = \frac{Q_{H} }{m(flow) * (h_{2} - h_{1}) }\\\\COP = \frac{4.38}{(0.022)*(273.31-244.5)}\\\\COP = 6.17[/tex]