The three phase full load secondary amperage is 2775.7 A
Explanation:
Following data is given,
S = Apparent Power = 1000 kVA
No. of phases = 3
Secondary Voltage: 208 V/120 V (Here 208 V is three phase voltage and 120 V is single phase voltage)
Since,
[tex]V_{1ph} =\frac{ V_{3ph}}{\sqrt{3} }\\V_{1ph) = \frac{208}{\sqrt{3} }\\[/tex]
[tex]V_{1ph} = 120 V[/tex]
The formula for apparent power in three phase system is given as:
[tex]S = \sqrt{3} VI[/tex]
Where:
S = Apparent Power
V = Line Voltage
I = Line Current
In order to calculate the Current on Secondary Side, substituting values in above formula,
[tex]1000 kVA = \sqrt{3} * (208) * (I)\\1000 * 1000 = \sqrt{3} * (208) * (I)\\I = \frac{1000 * 1000}{\sqrt{3} * (208) }\\ I = 2775.7 A[/tex]